Toshiba 1600EP SERIES Instruction Manual page 40

Hide thumbs Also See for 1600EP SERIES:
Table of Contents

Advertisement

Data Setting Screens (Cont'd)
The following screens show the setting procedure for setting the data variables. They are accessed from
the main 'Data Setting Screens' (see
AUTO RETRAN: YES
TO ACCEPT:SET
AUTO RETRAN: NO
TO ACCEPT:SET
Loops through both
possibilities
REMOTE:BYPASS
TO ACCEPT:SET
REMOTE:SYSDWN
TO ACCEPT:SET
Loops through both
possibilities
COMM MODE: RS232
TO ACCEPT:SET
COMM MODE: SNMP
TO ACCEPT:SET
Loops through both
possibilities
INI BATT TST: YES
TO ACCEPT:SET
INI BATT TST: NO
TO ACCEPT:SET
Loops through both
possibilities
40
page
38) when the "SHIFT/SELECT" key is pressed:
Shift
Set
AUTO RETRAN: YES
+
TO CHANGE: SELECT
Monitor
Select
AUTO RETRAN: NO
Shift
Set
+
TO CHANGE:SELECT
Monitor
Select
Returns to Data Setting
Screens (with new
value applied)
Shift
Set
REMOTE:BYPASS
+
TO CHANGE: SELECT
Monitor
Select
REMOTE:SYSDWN
Shift
Set
+
TO CHANGE:SELECT
Monitor
Select
Returns to Data Setting
Screens (with new
value applied)
Shift
Set
COMM MODE: RS232
+
TO CHANGE: SELECT
Monitor
Select
Shift
Set
COMM MODE: SNMP
+
TO CHANGE:SELECT
Monitor
Select
Returns to Data Setting
Screens (with new value
Shift
Set
INI BATT TST: YES
+
TO CHANGE: SELECT
Monitor
Select
Shift
Set
INI BATT TST: NO
+
TO CHANGE:SELECT
Monitor
Select
Returns to Data Setting
Screens (with new value
Set to "Yes", the unit will automatically
retransfer back to UPS mode after
transferring momentarily to bypass mode
to prevent a sag in the output due to an
instantaneous load change. If set to
"No", the unit will attempt to ride out the
load change and the output voltage
could be decreased momentarily.
Default setting is YES.
This setting uses the remote switch to
place the unit to bypass mode.
This setting uses the remote switch to
shut the output of the unit off. While off,
the online LED will be flashing and the
LCD will display the message:
OUTPUT SHUTDOWN
The remote switch connection is on the
rear terminal block at positions 11 and
12. The unit will transfer 2 secs. after
closing the remote switch and will return
to UPS mode 2 secs. after the switch
opens. Default setting is BYPASS
This setting selects the RS232 as the
communication port, SNMP is disabled.
This setting selects the SNMP as the
communication port, RS232 is disabled.
Default setting is SNMP.
applied)
Set to "YES", the unit will perform a
battery test the first time the unit
transfers to On Line. If Auto Run (see
page 33) is set to YES then the battery
test will be done at power up.
Default setting is NO.
applied)
1600EP Series Instruction Manual