21. Optional Receptacle Panel Installation Instructions

These are the instructions for installing the optional Modular Output Receptacle Panels for the 1600XP
Series UPS. These instructions apply to all UH3-RP-XX panel options.
WARNING: The work outlined in these instructions is to be performed only on a completely un-energized
UPS system.
Refer to Figure 1 for location of UPS referenced material. Refer to Figure 2 for material referring to the
receptacle panel module. There are different panels available depending on the UPS typeform.
Step 1: Remove the modular receptacle panel cover plate.
On the rear of the UPS, locate the cover plate for the receptacle panel module interface
(see Figure 1).
Remove the 6 mounting screws.
Remove the cover plate. A square-shaped plug will be exposed.
Step 2: Snap-In Output Receptacle modular panel.
Carefully mate the square-shaped connector on the UPS to its matching counter part on the rear
of the modular panel.
Step 3: Mount the receptacle panel.
Attach the screws removed from the cover plate through the mounting holes of the receptacle
panels and back into the UPS mounting points.
Mounting
Mounting
Screws
Figure 1
1600XP Series Installation and Operation Manual
Receptacle
Panel
Connector
Figure 2
45