Toshiba 1600EP SERIES Instruction Manual page 24

Hide thumbs Also See for 1600EP SERIES:
Table of Contents

Advertisement

Capacity
Environment
Operating temperature
(15 – 25° C recommended)
Storage Temperature
Installation Area
Operating Humidity
Altitude
Acoustical Noise
Heat Generation
Operation Diagnosis
Battery Check
Input OV Protection
Battery Lifetime
Internal Temperature
Event Data Storage
Applications
Switches
Bypass Switch
Bypass Disable
Automatic Retransfer
User Interface
Real Time Clock
Schedule Operation
RUN/STOP Disable
Autostart
Remote ON/OFF
LED Display
LCD Screen
UPS Operation: 6 Keys
Buzzer Volume
Power Connections
Emergency Power Off
Remote Contacts
RS232 ASCII Interface
24
STANDARD MODELS: 10kVA; 14kVA; 18KVA; 22kVA (CONT'D)
10kVA (8.5kW)*
14kVA (11.9kW)*
To be installed in a well ventilated area free of airborne dust,
metal particles or fl ammable gas, allow at least 4 inches on all sides
50 dB (A) maximum @ 1 meter from front panel
4352 BTU/Hr
Performed on start up, by schedule, on-demand (user confi gurable)
UPS calculates battery replacement time based upon
battery ambient temperature (LCD display, LED and beeps)
UPS gives indication of internal temperature, alarm when high temp
64-Supply Mode, 32-Back up, 16- Faults
Static switch <1/4 cycle (50Hz:5ms/60Hz:4.16ms)
Factory or authorized service center selectable only
Provided (can be disabled from front panel)
Standard, Minimum 3 days memory backup during power loss
Schedule ON/OFF operation of UPS using communication software
UPS has option for UPS to start automatically when AC is applied
4 LED's indicating input/output condition, warning and battery operation
Run/Stop, Set/Monitor, Shift/Select,
Low, High, Mute; Selectable by keypad
Standard (INV, BYP, BATT, LB, AC, FLT)
18kVA (15.3kW)*
60 Hz (0 – 40 °C) ; 50Hz (0 – 33 °C)
-20 – 40 °C (-4 to 104 °F)
30 – 90% (no condensation)
< 1000m above sea level****
6092 BTU/Hr
7832 BTU/Hr
Standard
Generator compatible
Standard, external terminal
16 characters x 2 lines
Del/(page
Hard wire (Standard)
Standard (Terminal contacts only)
Standard
22kVA (18.7kW)*
6900 BTU/Hr
down),
Reset/(page
1600EP Series Instruction Manual
up)