Data Setting Screens (Cont'd)
The following screens show the setting procedure for setting the data variables. They are accessed from
the main 'Data Setting Screens' (see
TO BEGIN:SET
OR
BATTERY TEST
INHIBIT
VOLTAGE ADJ: +5
TO ACCEPT: SET
VOLTAGE ADJ: +0
TO ACCEPT: SET
VOLTAGE ADJ: -5
TO ACCEPT: SET
Loops through three
possibilities
CLEAR TIMER SET
TO ACCEPT: SET
DEFAULT SETTINGS
TO ACCEPT: SET
1600EP Series Instruction Manual
page
38) when the SHIFT/SELECT key is pressed:
Shift
BATTERY TEST
Set
+
Monitor
Select
Executes battery
test and returns
to Data Settings
Screens
Shift
Set
VOLTAGE ADJ: +5
+
TO CHANGE: SELECT
Monitor
Select
Shift
Set
VOLTAGE ADJ: +0
+
TO CHAGNE:SELECT
Monitor
Select
Shift
Set
VOLTAGE ADJ: -5
+
Monitor
TO CHANGE: SELECT
Select
Returns to Data Settings
Screens (with new value
applied)
CLEAR TIMER SET
Shift
Set
+
TO CHANGE:SELECT
Monitor
Select
Executes battery test
and returns to Data
Settings Screens
Shift
DEFAULT SETTINGS
Set
+
TO CHANGE:SELECT
Monitor
Select
Executes battery test
and returns to Data
Settings Screens
This parameter has no options to set. A
battery test will be performed once the
SHIFT + SET button is pressed.
###%
If the BAT TEST INHIBIT message is
displayed, it indicated that a battery test
has been performed recently. The UPS
will not allow frequent battery tests to
insure that the batteries remain in a fully
charged state.
This parameter allows the user to offset
the output voltage (while the unit is
running on-line), by 1% increments
between -5% to +5%.
Default value is +0
This parameter has no options to set.
Pressing the SHIFT + SET button while
this message is displayed will cancel
timer setting.
43