4.3 Mounting

4.3.1

Position of the boiler

Location of the installation
GTU C 330 boilers must be installed in a frost-free room.
In order to avoid damage to the boiler, it is necessary to
prevent the contamination of combustion air by chlorine
and/or fluoride compounds, which are particularly
corrosive. These compounds are present, for example, in
aerosol sprays, paints, solvents, cleaning products,
washing products, detergents, glues, snow clearing salts,
etc.
Therefore:
- Do not suck in air evacuated from premises using such
products: hairdressing salons, dry cleaners, industrial
premises (solvents), premises containing refrigeration
systems (risk of refrigerant leakage), etc.
- Do not stock such products close to the boilers.
If the boiler and/or peripheral equipment are corroded by
such chloride or fluoride compounds, the contractual
guarantee cannot be applied.
The warranty does not apply to damage to the boiler caused by these
instances. If the heating device is installed in residential premises
where people are present all the time, it is necessary to use a
concentric ambient air inlet / combustion gas evacuation installation.
When installing the boiler, it is necessary to comply with degree of
protection IP21.
16
GTU C 330
07/04/2009 - 300016152-001-C