4.5.5
Safety valve
The safety valve must be connected to the boiler outlet and no other
valve or flap must be interposed between it and the boiler.
Minimum safety valve flowrate as a function of maximum boiler nominal output :
Minimum relieving capacity
Maximum gross boiler output
(a) = kW, (b) = Kg/h, (c) = MBtu/h, (d) = lb/h
4.5.6
Connecting the condensates discharge conduit
It is imperative that a siphon (optional equipment) be connected to
the condensates discharge pipe to prevent any leakage of
combustion products.
The condensates in oil-fired condensing boilers are acidic. We
recommend the installation of a condensates neutralisation system to
protect the pipes and the environment.
07/04/2009 - 300016152-001-C
Example
Maximum boiler nominal output is 200 kW.
Minimum safety valve flowrate must be 1500 Kg/h
GTU C 330