30 Answer anytime (Default)
When using a DC58M digi-modem, the
digi-modem will always attempt to answer
incoming calls.
Answer o/p 1 on
The digi-modem will only attempt to answer
incoming calls when "Custom Output 1" is
on.
31 NVM is Unlocked (Default)
The NVM can be reset to the factory
defaults by shorting the FACTORY RESTART
pins during power-up.
NVM is Locked
The NVM cannot be reset by shorting the
FACTORY RESTART.
+
If the "NVM is LOCKED" option is selected it is
imperative that the engineer code is not lost or
forgotten. If this is the case then the only way of
returning the system to its factory default setting
is by returning the control panel PCB to Menvier
Security.
32 Unshunt. no exit (Default)
The use of a shunt code to reinstated a
selected group of circuits will not initiate the
exit procedure.
Unshunt & exit
The use of a shunt code to reinstated a
selected group of circuits will initiate the exit
procedure.
33 Ignore errors (Default)
When attempting to set with one or more
circuits in fault the system will continue with
the exit procedure but will display the
circuits that are in fault. If the circuits are
not cleared at the end of the exit
procedure a set fail condition will occur.
View exit errors
When attempting to set with one or more
circuits in a fault the system will prompt the
user that a fault exists and the display will
scroll through the circuits that are in fault.
Once the faulty circuits are cleared the
user will be prompted to press [ENT] to
continue with the exit procedure.
34 Mimic. All times (Default)
When using output modules or outputs that
are programmed as circuit mimic, the
outputs will mimic the circuit at all times.
Mimic. Set only
When using output modules or outputs that
are programmed as circuit mimic, the
outputs will only mimic the circuit if the
circuit is in a set ward.
35 Entry Keypad Lock
When programmed as "Yes" then users
cannot unset the system from a keypad
during entry. Program this option as "Yes" if
you are installing a system to comply with
DD243:2002 paras 6.4.5 and 6.4.6. (The
user must unset the system with a proximity
tag ("Portable ACE") or the ARC unsets the
system.)
When programmed as "No" then users can
unset the system from a keypad during
entry.
(Default = No)
36 Sounder on Confirm
When programmed as "Yes" the control unit
activates the internal sounders after a
confirmed alarm and any programmed
bell delay. When programmed as "No" the
control unit starts the internal sounders
immediately after an unconfirmed alarm.
(Default = No)
37 Bells on Confirm
When programmed as "Yes" the control unit
activates the external sounders after a
confirmed alarm and any programmed
bell delay. When programmed as "No" the
control unit activates the external bell
immediately after an unconfirmed alarm.
(Default = No)
38 Confirmation After Entry
When programmed as "Yes" the control unit
sends a confirmed alarm if the intruder
activates one or two separate zones after
the entry timer expires. To select between
one or two zones use "39 Entry
Confirmation After 2 circuits" When
programmed as "No" the control unit
disables alarm confirmation when a user
starts the entry timer. Use the "No" option to
comply with DD243:2002 paras 6.4.2,
6.4.3, 6.4.4 and 6.4.6.
(Default = No)
Engineer's Menu 1