Manifold (Outgoing) & Inlet (Incoming) Pressure Check Procedures - kozy heat 55801 Duluth Installation & Operating Manual

Free-standing direct vent fireplace
Table of Contents

Advertisement

IMPORTANT NOTICE: A pressure check tap for both the manifold (outgoing) and inlet (incoming) pressure has
been incorporated into the valve by Honeywell. The right pressure tap is the manifold pressure and the left
pressure tap measures the incoming pressure. Follow the instructions below for proper pressure testing
procedures.
TO CHECK THE MANIFOLD PRESSURE:
1. Light pilot .
2. Loosen the manifold pressure tap [D] by turning the screw counter-clockwise.
3. Attach manometer to pressure tap using a 5/16" I.D. hose [F].
4. Turn black control knob [A] to the 'ON' position.
5. Turn the burner 'ON' by depressing the rocker switch [C] to the 'ON' position and note manometer reading.
6. Turn the rocker switch [C] to the 'OFF' position.
7. Disconnect manometer hose and tighten screw (clockwise). Screw should be snug, do not over tighten.
8. Attach manometer to manifold pressure tap to verify that it is completely sealed.
Manometer should read no pressure when the rocker switch is turned 'ON'.
NOTE: If manifold pressure reading is within the normal range, an incoming pressure check is not necessary. A
too high or too low pressure reading warrants an inlet (incoming) gas pressure check.
TO CHECK THE INLET PRESSURE:
1. Loosen Inlet pressure tap screw [E] by turning screw counter-clockwise.
2. Attach manometer using a 5/16" I.D. hose [F].
3. Light the pilot.
4. Turn the black control knob [A] to the 'ON' position. (Burner should not come 'ON') and note manometer
reading.
5. Turn the rocker switch [C] to the 'ON' position by depressing the switch and check the pressure to ensure that
it stays near the maximum inlet pressure.
6. Turn the rocker switch [C] to the 'OFF' position.
7. Turn the pilot to the 'OFF' position.
8. Disconnect hose and tighten screw (clockwise). Screw should be snug, do not over tighten.
9. Relight pilot and turn the control knob [A] to the 'ON' position. Attach manometer to the inlet pressure tap
to verify that it is completely sealed. Manometer should read no pressure.
NOTE: If Inlet pressure reading is too high or too low, contact the gas company. Only a qualified gas service
technician should adjust the incoming gas pressure.
CAUTION: A LOW PRESSURE READING CAN CAUSE DELAYED IGNITION.
Figure 17
PRESSURE TESTING
MANIFOLD & INLET PRESSURE
Note: ON/OFF rocker switch is located on
the lower right frame of the fireplace.
Page 20