CONVERSION KIT INSTRUCTIONS
CONVERT GAS VALVE:
Follow instructions included with kit to convert gas valve to either Nat. or LP.
COMPLETE THE CONVERSION:
1.
Adjust venturi on burner tube to correct setting by loosening screw,
adjusting cap and retightening screw.
CORRECT SETTINGS: NAT. : 1/4" (6mm) open
2.
Re-install burner tube into fireplace, checking to ensure burner venturi is
properly seated over burner orifice.
3.
Re-install pilot shield and log set.
4.
Light pilot and turn burner on. Pages 7-9.
5.
Test both inlet and manifold pressures following procedure as outlined on
page 10. Chart below states proper pressure readings.
6.
Visually check for leaks at all connections with soapy water, whether field
or factory made. Check pilot flame. Flame should envelope top of
thermocouple and thermopile 3/8" (10mm) to 1/2" (13mm), and extend onto
burner far enough for proper ignition.
To Adjust pilot: Remove pilot adjustment screw from gas valve. Turn in-
ner pilot adjustment screw clockwise to decrease or counter-clockwise to
increase pilot flame. Re-install pilot adjustment screw cover and tighten.
7.
Turn burner and pilot off.
8.
Affix Gas sticker over existing label on metal tag.
9.
Re-install glass frame assembly and upper grill.
10. Verify proper ignition and operation of fireplace. Refer to page 16 for
proper pilot and burner flame appearance and adjustment.
11. Complete and affix 'Gas Conversion' label as close to rating plate as
possible.
* REFER TO FIREPLACE INSTALLATION MANUAL IF NECESSARY.
MINIMUM INLET GAS PRESSURE
MAXIMUM INLET GAS PRESSURE
MANIFOLD PRESSURE (HI)
MANIFOLD PRESSURE (LO)
L.P. : 1/2" (13mm) open
NATURAL GAS
5" WC (1.25 kPa) (7" WC (1.74 kPa) (recommended)
10.5" WC (2.62 kPa)
3.5" WC (.87 kPa)
1.6" WC (.40 kPa)
PROPER BURNER / PILOT ASSEMBLY ORIENTATION
(shown without pilot shield for clarity purposes)
Figure 15a
PROPER BURNER TUBE VENTURI /ORIFICE
PLACEMENT
Figure 15b
GAS CONVERSION LABEL
(included with conversion kit)
Figure 15c
LP GAS
11" WC (2.74 kPa) (recommended)
13" WC (3.24 kPa)
10" WC (2.49 kPa)
6.3" WC (1.57 kPa)
15