Horizontal sections require 1/4" (6mm) rise for every 12" (305mm) of travel.
Page 17 has information on restrictor installation in conjunction with venting installation. Page 31 has information on restrictor
recommendations depending on burner flame appearance and instructions on installation after venting is completed.
NOTE
(2) 45° degree elbows may be used in place of (1) 90° elbow.
For each additional 90° elbow used after first elbow, 3ft. (914mm) must be subtracted from maximum allowed venting.
CAUTION
This gas appliance must not be connected to or joined with any other chimney flue serving another appliance.
WARNING
A WALL PASS-THRU MUST BE USED ON ALL HORIZONTAL VENT RUNS.
MIN. / MAX. VERTICAL VENTING
TERMINATION CAP
MINIMUM: 0"
(0mm)
MAXIMUM: 28ft. (8.53m)
Figure 19a
VENTING
90° ELBOW
HOR. / VERT. COMBINATION
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
(12.9m)
40
38
36
34
32
30
28
26
24
22
(6.1m)
20
18
16
14
12
10
8
6
4
2
(ft.)
0
Figure 19b
18
Termination must be
within shaded area