Troubleshooting
LED and audible alarm troubleshooting
The DirectFlow UPS is designed for durable, automatic operation and also to alert you whenever potential
operating problems might occur. The alarms do not necessarily mean that the output power is affected;
instead, they are often preventive alarms intended to alert you of a possible condition. An operating problem
might trigger the following activity:
•
An audible alarm announced by a buzzer in the power unit
•
LEDs illuminating, flashing, or not illuminating on the control panel
•
Alarm descriptions that appear on the LCD screen
•
Alarm entries or related event entries that appear on the Alarms screen or the Event Log screen of the
Management Module web interface
The following table describes typical alarms and conditions that are accompanied by LED behavior on the
power unit front panel.
LED
UPS fault LED
Bypass mode LED
Battery mode LED
Input LED
Power LED (on
Management Module
card)
Health/Alert LED (on
Management Module
card)
The alarm descriptions table describes typical alarms and conditions that appear on the power unit front
panel LCD screen in the UPS event log. If an alarm appears with a service code, see "HP contact information
(on page 120)."
LED status
Solid red light indicates a
UPS fault
Solid green light indicates
the UPS is in Bypass mode
•
Solid yellow light
indicates the UPS is in
Battery mode
•
Flashing yellow light
indicates low battery
condition
No light indicates utility
power is out of operating
range
No light indicates the card
is not active
Red light indicates an error
in the card boot process
Alarm type
Long buzzer (5 sec)
none
•
Short buzzer (.1 sec)
upon entering Battery
mode or low battery
status
•
Long buzzer upon
transferring out of
Battery mode (5 sec)
or low battery
condition (1 sec)
none
none
none
Troubleshooting 89