Troubleshooting; Led And Audible Alarm Troubleshooting - HP R1500 - UPS XR User Manual

Hp r1500 g3 ups user guide
Table of Contents

Advertisement

Troubleshooting

LED and audible alarm troubleshooting

Condition
UPS operating from
utility
Buck mode (high
input voltage)
Boost mode (low
input voltage)
Over temperature
condition
Battery test failure
Fan failure
Output short circuit
Power up failure from
a DC start—Low
battery (no utility
power)
Low battery (no utility
power)
Online—UPS power
capacity exceeded
Overload timeout
On battery—Input
voltage is out of
range
On battery—No
utility power
On battery—Battery
voltage condition
On
battery—Overload
condition
On battery—Output
voltage is out of
range
On battery—Output
wave is abnormal
Power On
On Battery
Overload
LED
LED
LED
(green)
(yellow)
(red)
On
Off
Off
On
Off
Off
On
Off
Off
On
On
Off
Off
On
Off
On
Off
Off
On
On
On
Flashing
Flashing
Flashing
Off
On
Off
On
Off
On
Off
Off
On
On
On
Off
Off
On
Off
Flashing
Off
Off
Off
On
On
Off
Flashing
Off
Flashing
Flashing
Off
General
Audible alarm
Alarm LED
(red)
Off
No audible alarm
Off
No audible alarm
Off
No audible alarm
Flashing
On—Continuous
Flashing
On—Continuous
Flashing
On—Continuous
Flashing
On—Continuous
Flashing
On—3 beeps/10
seconds
Off
On—2 second
beep
Off
On—1 second
beep
Flashing
On—Continuous
Off
On—2 second
beep
Off
On— 4 second
beep
Flashing
On—Continuous
Off
On—1 second
beep
Flashing
On—Continuous
Flashing
On—Continuous
Can alarm
be silenced
("Silencing
an audible
alarm" on
page 20)?
N/A
N/A
N/A
No
Yes
No
No
No
No
No
No
Yes
Yes
Yes
No
No
No
Troubleshooting 31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R1500 g3

Table of Contents