Troubleshooting; Led And Audible Alarm Troubleshooting - HP R1500 - UPS XR User Manual

Hp ups r1500 g2 user guide
Table of Contents

Advertisement

Troubleshooting

LED and audible alarm troubleshooting

Condition
UPS operating from
utility
Buck mode (high
input voltage)
Boost mode (low
input voltage)
Over temperature
condition
Battery test failure
Fan failure
Output short circuit
Power up failure
from a DC start—
Low battery (no
utility power)
Low battery (no
utility power)
Online—UPS power
capacity exceeded
Overload timeout
On battery—Input
voltage is out of
range
On battery—No
utility power
On battery—Battery
voltage condition
On battery—
Overload condition
Power
On
Overloa
d LED
On LED
Battery
LED
(green)
(red)
(yellow)
On
Off
Off
On
Off
Off
On
Off
Off
On
On
Off
Off
On
Off
On
Off
Off
On
On
On
Flashing
Flashing
Flashing
Off
Flashing
Off
On
Off
On
Off
Off
On
On
On
Off
Off
On
Off
Flashing
Off
Off
Off
On
On
General
Audible alarm
Alarm LED
(red)
Off
No audible alarm
Off
No audible alarm
Off
No audible alarm
Flashing
On—Continuous
Flashing
On—Continuous
Flashing
On—Continuous
Flashing
On—Continuous
Flashing
On—3 beeps/10
seconds
Off
On—2 second
beep
Off
On—1 second
beep
Flashing
On—Continuous
Off
On—2 second
beep
Off
On— 4 second
beep
Flashing
On—Continuous
Off
On—1 second
beep
Can
alarm be
silenced
("Silencin
g an
audible
alarm"
on page
24)?
N/A
N/A
N/A
No
Yes
No
No
No
No
No
No
Yes
Yes
Yes
No
Troubleshooting 33