Power unit front panel controls
Item
Component
UPS fault LED
1
Bypass mode LED
2
Battery mode LED
3
Input LED
4
Up arrow
5
Down arrow
6
Off/ESC/Clear fault
7
button
On/Enter button
8
Description
Red light indicates a fault; no light indicates proper
function.
Green light indicates Bypass mode; no light
indicates AC mode.
Yellow light indicates Battery mode; flashing
indicates low battery.
Green light indicates that the power input is
adequate.
Press to scroll up through the menu structure.
Press to scroll down through the menu structure.
•
In AC mode, press the button for 3 seconds to
transfer the UPS to Bypass mode; in Battery
mode, press for 3 seconds to power down the
UPS output.
•
During menu selection, press the button to go
back to the previous menu.
•
During a UPS fault, press the button for 3
seconds to clear the fault and transfer the UPS
to Bypass mode.
Press the button for 3 seconds to power up the UPS
on; press the button to confirm setup or menu
entries.
Overview 12