Battery Runtime; Ups Input Specifications - HP R12000 User Manual

Directflow ups
Hide thumbs Also See for R12000:
Table of Contents

Advertisement

Feature
Charging

Battery runtime

Average battery runtime is approximate and varies depending on connected equipment, configuration,
battery age, temperature, and operating conditions. Estimated runtime is based on the batteries at beginning
of life.
Lead acid battery runtime
Power
415 kVA (4.5 kVA)
415 kVA (9 kVA)
415 kVA (12 kVA)
415 kVA (13.5 kVA) >4 min
415 kVA (15 kVA)
415 kVA (18 kVA)
Lithium-ion battery runtime
Power
415 VAC (3.75 kVA) >9:30 min
415 VAC (7.5 kVA)
415 VAC (11 kVA)
415 VAC (12 kVA)
415 VAC (15 kVA)

UPS input specifications

UPS model
power unit
NA/JPN
power unit INTL
The maximum load applies to linear/PFC loads.
Specification
Complete charge in no more than 2 hours; partial charge in
approximately 1 hour to reach 80 percent capacity at
default nominal utility voltage and no load.
48 V, 2 A
Runtime with one
battery pack
>13 min
>7 min
>4:30 min
>2:30 min
>2 min
Runtime with one
battery pack
>4:30 min
>2:30 min
>1:30 min
>1 min
Utility voltage
Available settings
frequency (Hz)
utility voltage (VAC)
50/60 Hz
480/415/400/380 V
+10/-15%
50/60 Hz
480/415/400/380 V
+10/-15%
Runtime with two
battery packs
>40 min
>18 min
>13 min
>11 min
>10 min
>7:30 min
Runtime with two
battery packs
>20 min
>10 min
>6:30 min
>6 min
>5 min
Dedicated
branch circuit
rating (A)
24 A
24 A
Line cord
480/415/400/380 V,
5-wire; PE 30 A cord and
plug
480/415/400/380 V,
5-wire, PE 30 A cord and
plug
Specifications 114

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R18000

Table of Contents