HP R12000 User Manual page 96

Directflow ups
Hide thumbs Also See for R12000:
Table of Contents

Advertisement

Deep Sleep mode
setting
The UPS sets "Enter Deep
Sleep Mode."
The UPS clears "Enter
Deep Sleep Mode."
Reset the power on the power module to avoid dropping loads during troubleshooting.
Set the power module to Bypass mode.
1.
Disconnect the power module.
2.
Reconnect the power module.
3.
Set the power module to Normal mode.
4.
Charger Limit is set to
Charger Limit is set to
any setting except
NO CHARGE and a
NO CHARGE
battery module has low
voltage
Keep at Deep Sleep
Keep at Deep Sleep
mode.
mode.
Wake up.
Keep at Deep Sleep mode
until the handle of the
battery module is pressed
and the low-voltage
battery module is
replaced.
Charger Limit is set to NO
CHARGE and no battery
modules have low voltage
Keep at Deep Sleep mode.
Wake up.
Troubleshooting 96