5. Maintenance

5.1 Troubleshooting

Operation status
Batteries disconnected
Overload
End of battery life
Event
UPS fault

5.2 Updating the UPS firmware

To update the UPS firmware, see the HP website (http://www.hp.com/go/rackandpower).
Page 26
Possible cause
The UPS does not recognize
the internal batteries
The batteries are disconnected
Power requirements exceeds the
UPS capacity (greater than 105 %
of nominal)
The end of the battery life is
reached.
An UPS event occurs
Example:
The RPO contact has been activated
to shutdown the UPS and now
prevents restart.
The UPS has an internal fault
Action
If the condition persists, contact your
service representative
Verify that all batteries are properly
connected. If the condition persists,
contact your service representative.
Remove some of the equipment
from the UPS. The UPS continues to
operate, but may shutdown if
the load increases. The alarm resets
when the condition becomes
inactive.
Contact your service representative
for battery replacement.
For this event, set the contact back
to its normal position and press the
button to restart.
The UPS does not protect the
equipment.
Note: Record the alarm message
and the UPS Serial Number, then
contact your service representa-
tive.
792519-001 Edition 1