GE NetworX V3 Installation Manual page 110

Alarm system
Table of Contents

Advertisement

110
NetworX Version 3 Installation Manual
(*) Note: This feature is only used when the GSM module is enrolled by the panel and if the GSM module is used as
backup (GSM voice channel) for the PSTN dialer of the panel. Also telephone line monitoring needs to be
enabled in location 40. Do not use this feature as the only backup feature of the PSTN dialer but use this in
addition with the standard backup options as described in the GSM module manual.
LOCATION 38 - SWINGER SHUTDOWN COUNT
Location 38 contains the number of trips on a zone before that zone will be automatically bypassed.
From 0 to 255. Refer to the feature definitions.
LOCATION 39 - KEYPAD SOUNDER CONTROL (1 segment, feature selection data)
Segment 1
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
LOCATION 40 - SYSTEM TIMERS (14 segments, numerical data)
Location 40 contains the duration of various system timing functions. Example: If you want the
duration of the dynamic battery test to be 30 minutes, you should program [3]- [0]-[*] in segment 1
of this location. The [3]-[0] is the number of minutes; the [*] stores the data, and moves to the next
segment of this location.
Segment 1
Dynamic battery test duration in minutes, 0-30 minutes ("0" = no test)
Segment 2
AC fail report delay in minutes, 0-255 minutes
Segment 3
Power up delay in seconds, 0-60 seconds ("0" = no power up delay)
Segment 4
Siren time in minutes, 1-255 minutes
Segment 5
Telephone line cut delay in seconds, 0-255 seconds ("0" = no telephone line
monitoring enabled)
Segment 6
Cross zone time in minutes, 0-255 ("0" = no cross zoning)
Segment 7
Chime time in 50 ms. (1/ 20th second) increments from 0-12 seconds ("0" = follows
zone 255 latched)
Segment 8
Dial delay in seconds, 0-255 seconds (0 no abort delay)
Segment 9
Fire alarm verification time in seconds, 120-255 seconds ("0" = no fire alarm
verification). Values less than 120 s. are considered as 120 s.
Segment 10
Listen-in time in seconds, 0-255 (" 0" = no listen-in time)
Segment 11
Zone activity monitor feature timed in hours/days, 0-255 ("0" = disabled)
Segment 12
Auto arming warning timer, 1-255 minutes
Segment 13
Auto arming retry timer, 1-255 minutes
Segment 14
Programming Timeout, 1-255 minutes ("0" = 15 minutes)
LOCATION 41 - CODE REQUIREMENTS (1 segment, feature data)
Segment 1
1 =
On: if keypad sounds for "Telephone Line Cut" when the system is armed
On: if keypad sounds for "Telephone Line Cut" when disarmed
On: if keypad sounds for an AC power failure
On: if keypad sounds when a low battery is detected
On: if keypad sounds during cross zone trip time
On: if keypad sounds for zone and box tampers
On: if keypad sounds for Emergency keys
Expander trouble
On: enables the 6-digit code option. If 6-digit option is enabled, all

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents