Segment 2
1 =
On: if siren driver should be a voltage output. Off: if on-board siren driver is
enabled
2 =
On: if sirens* sound for expander trouble
3 =
On: for zones to restore immediately. Off: for zones to restore only when the
siren is off or disarmed
4 =
On: if dynamic battery test is performed at arming. Off: if dynamic battery test
is performed at disarming (See location 40)
5 =
On: if battery missing test is performed every 12 seconds
6 =
On: if manual bell (BELL output, I/O and relays) test is performed during self
test function
7 =
On: if manual communicator test is performed during self test function
8 =
On: if Box Tamper terminals on the control panel are enabled
Segment 3
1 =
On: if box tamper report is enabled
2 =
On: if AC fail reporting is enabled
3 =
On: if low battery reporting is enabled
4 =
On: if Aux. power overcurrent report is enabled
5 =
On: if siren supervision report is enabled
6 =
On: if restore telephone line cut report is enabled
7 =
On: A+B Alarm. Off: cross-zoning
8 =
On: if expander trouble reporting is enabled
Segment 4
1 =
On: if fail to communicate report is enabled
2 =
On: if log full report is enabled
3 =
On: if autotest report is enabled
4 =
On: if start/end programming report is enabled
5 =
On: if end download report is enabled
6 =
On: if sensor low battery report is enabled
7 =
On: if sensor missing report is enabled
8 =
On: if autotest report is enabled ONLY when the system is armed
Segment 5
1 =
On: enable lost clock indication
2 =
Reserved
3 =
Reserved
4 =
On: will allow two trips on same cross-zone to activate an alarm
5 =
On: will not allow zones that are force armed to report bypass
6 =
On: enables silent exit option
7 =
On: activate "first disarm reporting" - "last arm reporting" for partitions
8 =
On: switch "summer/wintertime" and vice versa
Segment 6
1 =
Reserved
2 =
On: Use internal crystal for clock
3 =
On: zone activity monitor in hours (not in days)
4 =
On: enables first alarm logic
5 =
On: enables log protection
6 =
On: disables Clean Me report
7 =
On: siren* output is steady in case of fire alarm
8 =
On: valid user code will reset tamper memory
Segment 7
1 =
On: dial via GSM when phone line trouble (*)
2 =
On: Exit Error limited to Entry/Exit delay 1
3-8
Reserved
* BELL output only on NetworX V3
* BELL output only on NetworX V3
NetworX Version 3 Installation Manual
109