Clock; Table 10-31 Set-Up Group - Clock - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

10.7.22

Clock

Table 10-31 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Clock.
Parameter
Description
ID
Clock Hours
16
Clock Minutes
17
Clock Seconds
18
Clock Month
137
Clock Day
19
Clock Year
20
Time Zone (GMT)
21
Note: The Time Zone setting is used only for Email purposes, it has no other function.
10/05
Modbus Read, Write and Override Parameters plus Exception Codes
Table 10-31 Set-up Group – Clock
Register
Address
Hex
Decimal
4010
16400
FP
4011
16401
FP
4012
16402
FP
4089
16521
INT
4013
16403
FP
4014
16404
FP
4015
16405
FP
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
Enumerated Selection
R/W
0 to 23
R/W
0 to 59
R/W
0 to 59
R/W
0 = Unused
1 = January
2 = February
3 = March
4 = April
5 = May
6 = June
7 = July
8 = August
9 = September
10 = October
11 = November
12 = December
R/W
1 to 31
R/W
2005 to 2099
R/W
-1200 to +1300 (hours and
minutes away from GMT)
Data Range or
397