Modbus Read, Write and Override Parameters plus Exception Codes
10.7.7

Logic

Table 10-16 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Logic
Parameter
Description
Logic Gates
Gate 1 Type
Gate 2 Type
Gate 3 Type
Gate 4 Type
Gate 5 Type
Gate 1 InputA
(OR, NOR,
AND, NAND, X
OR, X NOR)
358
Table 10-16 Set-up Group – Logic
Register
Address
ID
Hex
Decimal
150
4096
16534
151
4097
16535
155
409B
16539
159
409F
16543
163
40A3
16547
167
40A7
16551
152
4098
16536
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
Enumerated Selection
INT
R/W
0 = Disable
1 = Enable
INT
R/W
0 = Not Used
1 = OR
2 = NOR
3 = AND
4 = NAND
5 = XOR
6 = XNOR
7 = B LT A
8 = B GT A
INT
R/W
Same as ID 151
INT
R/W
Same as ID 151
INT
R/W
Same as ID 151
INT
R/W
Same as ID 151
INT
R/W
0 = Digital Input 1
1 = Digital Input 2
2 = Digital Input 3
3 = Digital Input 4
4 = Relay 1
5 = Relay 2
6 = Relay 3
7 = Relay 4
8 = Relay 5
9 = Gate Out 1
10 = Gate Out 2
11 = Gate Out 3
12 = Gate Out 4
13 = Gate Out 5
14 = FIX ON
15 = FIX OFF
16 = MA MODE
17 = LR SPL1
18 = ADAPT1
19 = MA MODE2
20 = LR SPL2
21 = ADAPT2
Data Range or