Time Event; Table 10-29 Set-Up Group - Time Event - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Modbus Read, Write and Override Parameters plus Exception Codes
10.7.20

Time Event

Table 10-29 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Time Event.
Parameter
Description
Time Event 1
Time Event 1
Calendar Type
Time Event 1
Hour
Time Event 1
Minutes
Time Event 1
Month
Time Event 1
Days
394
Table 10-29 Set-up Group – Time Event
Register
Address
ID
Hex
Decimal
184
40B8
16568
185
40B9
16569
97
4061
16481
98
4062
16482
186
40BA
16570
99
4063
16483
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
Enumerated Selection
0 = None
INT
R/W
1 = Alarm 1 SP2
2 = Alarm 2 SP2
3 = Alarm 3 SP2
4 = Alarm 4 SP2
5 = STrSP/R
6 = Timer
7 = Auto
8 = MAN FS
9 = Use SP1
10 = Use SP2
0 = 5 Day Week
INT
R/W
1 = 7 Day Week
2 = Day of Week
3 = Calendar
0 to 23
FP
R/W
FP
R/W
0 to 59
INT
R/W
0 = Unused
1 = January
2 = February
3 = March
4 = April
5 = May
6 = June
7 = July
8 = August
9 = September
10 = October
11 = November
12 = December
FP
R/W
1 to 31
Data Range or
10/05