Modbus Read, Write and Override Parameters plus Exception Codes
10.7.2

Tuning Loop2

Table 10-11 lists all the register addresses and ranges or selections for the function
parameters in the Set-up Group – Tuning Loop 2.
Parameter
Description
ID
Gain #5 or PB
1
Note 1
Rate #5
2
Note 1
Reset #5
3
Note 1
Manual Reset
13
Gain #6 or PB
4
Note 1
Rate #6
5
Note 1
Reset #6
6
Note 1
Gain #7 or PB
23
Note 1
Rate #7
24
Note 1
Reset #7
25
Note 1
Gain #8 or PB
26
Note 1
Rate #8
27
Note 1
Reset #8
28
Note 1
Cycle Time #5
21
Cycle Time #6
22
340
Table 10-11 Set-up Group – Tuning Loop 2
Register
Data
Address
Type
Hex
Decimal
0101
257
FP
0102
258
FP
0103
259
FP
010D
269
FP
0104
260
FP
0105
261
FP
0106
262
FP
0117
279
FP
0118
280
FP
0119
281
FP
011A
282
FP
011B
283
FP
011C
284
FP
0115
277
FP
0116
278
FP
UDC3500 Universal Digital Controller Product Manual
Access
Data Range or
Enumerated Selection
R/W
0.001 to 1000 Gain
0.1 to 9999 PB
R/W
0.00 to 10.00
R/W
0.02 to 50.00
R/W
-100 to 100
R/W
0.001 to 1000 Gain
0.1 to 9999 PB
R/W
0.00 to 10.00
R/W
0.02 to 50.00
R/W
0.001 to 1000 Gain
0.1 to 9999 PB
R/W
0.00 to 10.00
R/W
0.02 to 50.00
R/W
0.001 to 1000 Gain
0.1 to 9999 PB
R/W
0.00 to 10.00
R/W
0.02 to 50.00
R/W
1 to 120 seconds
R/W
1 to 120 seconds