Setpoint Programming Event Alarms

An alarm setpoint can be configured to turn on or turn off an alarm based upon a
particular segment in a Setpoint Program.
Using Alarm 1 Setpoint 1 as an example:
If Alarm 1 Setpoint1 Value (A1S1 VAL) is configured for Segment 5, Alarm 1 Setpoint
1 Type (A1S1TYPE) is configured for Event On (EV ON) and Alarm 1 Segment 1
Event (A1S1 EV) is configured for BEGIN, then this alarm will activate when the
Setpoint Program reaches the beginning of Segment 5.
ATTENTION If no other alarm configuration turns this alarm off after the above
configuration has turned it on, then when the Setpoint Program is configured to be
disabled when the Setpoint Program ends, this alarm will stay on.
If Alarm 1 Setpoint1 Value (A1S1 VAL) is configured for Segment 5, Alarm 1 Setpoint
1 Type (A1S1TYPE) is configured for Event Off (EV OFF) and Alarm 1 Segment 1
Event (A1S1 EV) is configured for END, then this alarm will deactivate when the
Setpoint Program reaches the end of Segment 5.
ATTENTION Some other alarm configuration must first turn the alarm on before this
configuration can turn it off.