Real Time Clock; Inputs And Outputs - Honeywell Spyder Specification Data

Programmable controllers
Table of Contents

Advertisement

PUB6438S, PUB6438SR: 5.45 x 6.85 x 2.26 in. (13.84 x
17.40 x 5.74 cm)
Approval Bodies
UL/cUL (E87741) listed under UL916 (Standard for Open
Energy Management Equipment) with plenum rating.
CSA (LR95329-3) listed.
Meets FCC Part 15, Subpart B, Class B (radiated emissions)
requirements.
Meets Canadian standard C108.8 (radiated emissions).
Conforms to the following requirements per European
Consortium standards:
— EN 61000-6-1; 2001 (EU Immunity).
— EN 61000-6-3; 2001 (EU Emissions)
— BTL B-ASC (BACnet Testing Laboratories, BACnet
Application Specific Controller)

Real Time Clock

Operating Range: 24 hour, 365 day, multi-year calendar
including day of week and configuration for automatic day-
light savings time adjustment to occur at 2:00 a.m. local
time on configured start and stop dates
Power Failure Backup: 24 hours at 32°F to 100°F (0°C to
38°C), 22 hours at 100°F to 122°F (38°C to 50°C)
Accuracy: ±1 minute per month at 77° F (25° C)
Velocity Pressure Sensor
(PVB0000AS, PVB4022AS,
PVB4024NS, PVB6436AS, and
PVB6438NS)
Operating Range: 0 to 1.5 in. H
Series 60 Floating Actuator
(PVB0000AS, PVB4022AS, and
PVB6436AS)
Rotation Stroke: 95° ± 3° for CW or CCW opening dampers
Torque Rating: 44 lb-in. (5 Nm)
Run Time for 90° rotation: 90 seconds at 60 Hz
O (0 to 374 Pa)
2
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS

Inputs and Outputs

Each controller has four digital inputs (DI), six or eight digital
outputs (DO), three analog outputs (AO), and six universal
input (UI) circuits.
The PVB6436AS has only 6 digital Triac outputs available, the
PVB6438NS and PUB6438S each have eight digital Triac
outputs available, and PUB6438SR has eight digital relay
outputs available.
Digital Input (DI) Circuits
Voltage Rating: 0 to 30 Vdc open circuit
Input Type: Dry contact to detect open and closed circuit
Operating Range: Open circuit = False; Closed circuit = True
Resistance: Open circuit > 3,000 Ohms; Closed circuit < 500
Ohms
Digital Triac Output (DO) Circuits
Voltage Rating: 20 to 30 Vac @ 50-60Hz
Current Rating: 25 mA to 500 mA continuous, 800 mA
(AC rms) for 60 milliseconds
Digital Relay Output (DO) Circuits
(PUB6438SR only)
Voltage Rating: 20 to 30 Vac @ 50-60Hz
Current Rating: 0 mA to 1 A continuous, 3.5 A inrush
(AC rms) for 100 milliseconds
Analog Output (AO) Circuits
Analog outputs are individually configurable for current or
voltage.
ANALOG CURRENT OUTPUTS:
Current Output Range: 4.0 to 20.0 mA
Output Load Resistance: 550 Ohms maximum
ANALOG VOLTAGE OUTPUTS:
Voltage Output Range: 0.0 to 10.0 Vdc
Maximum Output Current: 10.0 mA
Analog outputs may be configured as digital outputs and
operate as follows:
– False (0%) produces 0 Vdc, (0 mA)
– True (100%) produces the maximum 11 Vdc, (22 mA)
3