Input 5; Table 10-22 Set-Up Group - Input 5 - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Modbus Read, Write and Override Parameters plus Exception Codes
10.7.13

Input 5

Table 10-22 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Input 5.
Parameter
Description
Input 5 Type
ATTENTION
Changing the Input Type will result in the loss of Field Calibration values and will restore
the Factory Calibration values.
Input 5
Transmitter
Characterization
Input 5 High
Range Value
372
Table 10-22 Set-up Group – Input 5
Register
Address
ID
Hex
Decimal
134
4086
16518
135
4087
16519
82
0052
82
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
Enumerated Selection
INT
R/W
0 = Disable
1 = 0-20mA
2 = 4-20mA
3 = 0-5V
4 = 1-5V
INT
R/W
0 = B TC
1 = E TC H
2 = E TC L
3 = J TC H
4 = J TC M
5 = J TC L
6 = K TC H
7 = K TC M
8 = K TC L
9 = NNM H
10 = NNM L
11 = Nicrosil H TC
12 = Nicrosil L TC
13 = Plat H
14 = Plat L
15 = R TC
16 = S TC
17 = T TC H
18 = T TC L
19 = W TC H
20 = W TC L
21 = 100 PT RTD
22 = 100 PT LO RTD
23 = 200 PT RTD
24 = 500 PT RTD
25 = 1000PT
26 = Radiamatic RH
27 = Radiamatic RI
28 = Linear
29 = Square Root
FP
R/W
–999. to 9999.
Engineering Units
Data Range or
10/05