Honeywell UDC3500 Product Manual page 113

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Function Prompt
Lower Display
RLYSTATE
RLY TYPE
MOTOR TI
OUT2 ALG
10/05
Selections or
Range of Setting
Upper Display
1OF 2OF
1ON 2OF
1OF 2ON
1ON 2ON
MECHAN
SOL ST
5 to 1800 seconds
NONE
TIME
CURRENT
TIME D
CUR D
CUR TI
TI CUR
UDC3500 Universal Digital Controller Product Manual
Parameter
Definition
DIGITAL OUTPUT STATUS AT 0 % OUTPUT—
Allows the following selections:
1OF 2OF
Output 1 de-energized
Output 2 de-energized
1ON 2OF
Output 1 energized
Output 2 de-energized
1OF 2ON
Output 1 de-energized
Output 2 energized
1ON 2ON
Output 1 energized
Output 2 energized
RELAY CYCLE TIME INCREMENT—Used only for
Time Simplex and Duplex output configurations. This
configuration sets the increment size of the relay
cycle times in the Tuning and Tuning 2 Set Up
groups.
ELECTROMECHANICAL RELAY—Cycle time in
one-second increments.
SOLID STATE RELAY—Cycle time in 1/3-second
increments. This is useful for solid-state relay
applications that require shorter cycle times. DO
NOT use this setting unless cycle times of less than
1 second are required.
ATTENTION The Lockout selection must be set to
NONE in order to view this selection.
MOTOR TIME—Appears only when "POSPROP" is
selected as the Output algorithm. This is the time it
takes the motor to travel from 0 to 100% (fully closed
to fully open). This time can usually be found on the
nameplate of the motor.
OUTPUT ALGORITHM—Selects the type of output
desired for the second control loop.
See OUT ALG for definitions.
NONE
TIME SIMPLEX
CURRENT SIMPLEX
TIME DUPLEX
CURRENT DUPLEX
CURRENT/TIME DUPLEX
TIME/CURRENT DUPLEX
ATTENTION Some of these configurations may not
be available on Loop 2 if Loop 1 uses the available
outputs. See Table 2-6 and Table 2-7 for information
about output types and how they are used for each
Loop.
Configuration
99