6.6 Restore Factory Output Calibration

Introduction
The factory calibration constants for the Current Outputs are stored in its non-volatile
memory. Thus, you can quickly restore the "Factory Calibration" for those outputs by
simply changing the CO RANGE setting for that output to the other setting and then
changing it back to the original type.
Refer to Table 6-8 Restore Factory Calibration for procedure
ATTENTION
A restored factory calibration overwrites any previous field calibration done for the output.
Protect your field calibration from accidental overwrites by configuring the appropriate
LOCKOUT selection after calibration.
See Section 3 – Configuration for specific instructions to set the lockout.
Step
Operation
1
Set LOCKOUT to
NONE
2
Enter OUTPUT
or OPTIONS
Setup Group
Scroll through
3
Functions
10/05

Table 6-8 Restore Factory Calibration

Press
until you see:
Setup
Setup
Upper Display = SET UP
Lower Display = TUNING
Until you see:
Func
Loop 1/2
Upper Display = one of the following:
NONE – all parameters are read/write
CALIB – all parameters are read/write except Calibration
+CONF – configuration parameters are Read Only; no
writes permitted
+VIEW – Tuning and Setpoint Ramp parameters are
read/write. No other parameters can be viewed.
ALL – Tuning and Setpoint Ramp parameters are available
for read only. No other parameters can be viewed.
Lower Display = LOCKOUT
Until NONE is in the upper display
or
until you see:
Setup
Setup
Upper Display = SET UP
Lower Display = OUTPUT (for First Current Output)
1. or –
Lower Display = OPTIONS (for Second or Third Current
until you see:
Func
Upper Display = the current selection
Loop 1/2
Lower Display = CO RANGE
to change the range configuration to the other selection
or
until the lower display rolls through the rest of the functions and
Func
returns to:
Loop 1/2
Upper Display = the new selection
Lower Display = CO RANGE
UDC3500 Universal Digital Controller Product Manual
Result
Outputs)
Output Calibration
285