Accutune; Table 10-13 Set-Up Group - Adaptive Tune - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Modbus Read, Write and Override Parameters plus Exception Codes
10.7.4

Accutune

Table 10-13 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Adaptive Tune.
Parameter
Description
Fuzzy Overshoot
Suppression
Fuzzy Overshoot
Suppression Loop2
Accutune Enable
Loop 1
Accutune Enable
Loop2
Accutune Duplex
selection
Accutune Error (Read
only) Loop1
Accutune Error (Read
only) Loop2
348
Table 10-13 Set-up Group – Adaptive Tune
Register
Address
ID
Hex
Decimal
193
00C1
193
193
01C1
449
152
0098
152
152
0198
408
225
00E1
225
151
0097
151
151
0197
407
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
Enumerated Selection
INT
R/W
0 = Disabled
1 = Enabled
INT
R/W
0 = Disabled
1 = Enable 1
2 = Enable 2
3 = Enable 12
INT
R/W
0 = Accutune Disabled
1 = Limit Tune
2 = SP Tune
3 = Tune + SP
4 = SP Tune + PV
Int
R/W
0 = Accutune Disabled
1 = Limit Tune
2 = SP Tune
3 = Tune + SP
4 = SP Tune + PV
INT
R/W
0 = Manual
1 = Auto
2 = Disable (blend)
INT
R/W
0 = None
1 = Output Limits
2 = PV Change
Insufficient
3 = Process
Identification Failed
4 = Accutune Aborted
5 = Running
6 = Setpoint Error
INT
R/W
0 = None
1 = Output > or < Output
Limits or Man Step=0
2 = PV Change
Insufficient
3 = Process
Identification Failed
4 = Accutune Aborted
5 = Running
6 = Setpoint Error
Data Range or
10/05