5.5 Input Calibration Procedure

Preliminary Steps
• Apply power and allow the controller to warm up for 30 minutes before you calibrate.
• Please read Subsection 5.3 before beginning the procedure.
• Make sure you have LOCK set to NONE. See Subsection 3.4 – Loop 1 Tuning Set
Up Group.
• See Table 5-1 for Voltage vs. Resistance equivalents or 0 % and 100 % range values.
CAUTION
For linear inputs, avoid step changes in inputs. Vary smoothly from initial value to final 100 % value.
Procedure
The calibration procedure for Input #1 or 2 is listed in Table 5-12.
Step
Operation
1
Enter Calibration
Mode
2
Calibrate 0 %
10/05

Table 5-12 Input Calibration Procedure

Press
Upper Display = CALIB
Setup
Setup
Lower Display = INPUTn [n=1 to 5]
until you see
You will see:
Func
Loop 1/2
Upper Display = DISABLE
Lower Display = CAL INn [n=1 to 5]
The calibration sequence is enabled and you will see:
or
Upper Display = BEGIN
Lower Display = CAL INn [n=1 to 5]
At the completion of the sequence, the selection
automatically reverts to disable.
You will see:
Func
Loop 1/2
Upper Display = APPLY
Lower Display = INn ZERO [n=1 to 5]
Adjust your calibration device to an output signal equal
to the 0 % range value for your particular input sensor.
See Table 5-1 for Voltage, Degrees, or Resistance
equivalents for 0 % range values.
Wait 15 seconds, then go to the next step.