Figure 2-10 Current Output Current/Time Duplex, Time/Current Duplex, Position Proportional Or Three Position Step Control; Figure 2-11 Auxiliary Output And Three-Relay Output - Honeywell DC33XB User Manual

Table of Contents

Advertisement

Installation
Current Output/Universal Output
Figure 2-10 shows the Output and Alarm wiring connections for models with Current
Output and two-relay outputs (Model DC330X-KE-XXX).
See Table 2-3 for relay terminal
connections for Output Algorithm
selected.
For Duplex Current
Output use Auxiliary
Output for Output 2
(cool) (see Figure 2-14).
ATTENTION:
All current outputs are
isolated from each
other, case ground, and
all inputs.
Electromechanical relays are rated at 5 Amps @120 Vac or 2.5 Amps at 240 Vac .
1
Customer should size fuses accordingly. Use Fast Blo fuses only.
Relays are NOT available on DC330X-C0-
Figure 2-10 Current Output Current/Time Duplex, Time/Current Duplex, Position
Figure 2-11 shows the Output and Alarm wiring connections for models with a
Current Output (Auxiliary Output) and three Relay Outputs (Model
DC330X-EE-2XX).
Auxiliary
Load
+
0-1000
Connect
shield to
ground at
one end
only
1
Alarm #2 is not available with Time Proportional Duplex or Three Position Step Control or Position Proportional Control.
2
Electromechanical relays are rated at 5 Amps @120 Vac or 2.5 Amps at 240 Vac.
Customer should size fuses accordingly. Use Fast Blo fuses only.
All current outputs are isolated from each other, case ground, and all inputs.

Figure 2-11 Auxiliary Output and Three-Relay Output

12
1
2
3
4
Output#1
N.C.
or
5
Alarm#2
N.O.
Relay
6
7
Output#2
N.C.
or
8
Alarm#1
N.O.
Relay
9
Proportional or Three Position Step Control
1
N.C.
Output
2
Relay#1
N.O.
3
4
Output
N.C.
Relay#2
5
N.O.
6
Alarm
Relay#1
16 +
7
N.C.
17 –
8
N.O.
9
UDC3300 Basic Model: DC33XB User Manual
+
Current Output
Controller Load
4–20 mA
0–1000 Ohms
Output or Alarm
Relay 2 Load
To terminal
4 or 6
Output or Alarm
Relay 3 Load
To terminal
7 or 9
Relay Load
To terminal
1 or 3
Relay Load
1
To terminal
4 or 6
Alarm Relay #1 Load
To terminal
7 or 9
Load
Supply
Power
1
Load
Supply
Power
1
Load
Supply
Power
2
Load
Supply
Power
2
Load
Supply
Power
2
24160
12/00