Setting The Ceiling Height - Daikin FCQ35B7V1 Service Manual

Hide thumbs Also See for FCQ35B7V1:
Table of Contents

Advertisement

ESIE05-04
2.6

Setting the Ceiling Height

Incorrectly setting
If you set the controller incorrectly, a connection mistake malfunction "UA" will appear on the remote
controller display.
See 'Malfunctioning Field Setting Switch (UA)' on page 3–50.
Mode No. 13 or 23
Set the second code No., according to the tables below.
First code No. 0
FHQ
Second code No.
01
02
03
FAQ
Second code No.
01
02
03
FCQ and FUQ
Indoor unit
FCQ35-71
FCQ100-125-140
FUQ
Part 4 – Commissioning and Test Run
Ceiling-suspended type
Height < 2.7 m
2.7 m < height < 3.5 m
Not used
Wall-mounted type
Normal
High
Extra high
Second code No.
4-way outlet
01
< 2.7 m
02
< 3.0 m
03
< 3.5 m
01
< 3.2 m
02
< 3.6 m
03
< 4.2 m
01
< 2.7 m
02
< 3.0 m
03
< 3.5 m
Field Settings
3-way outlet
2-way outlet
< 3.0 m
< 3.5 m
< 3.3 m
< 3.8 m
< 3.5 m
< 3.6 m
< 4.2 m
< 4.0 m
< 4.2 m
< 4.2 m
< 3.0 m
< 3.5 m
< 3.5 m
< 3.8 m
< 3.8 m
1
3
4
5
4–15