Installing Options and Accessories

6.4 Installing a Remote Monitor Panel

NOTE
Card at one time (see Table 6-1).
Table 6-1. Optional Monitoring Accessories
To install RMP wiring, perform the following procedure:
1. Verify the UPS system is turned off and all power sources are removed. See
2. Perform procedures listed in paragraphs 6.1 and 6.2.
NOTE
the wall. Do not use hollow wall anchors.
3. Securely mount the RMP at the desired location. See drawing 164201535-11 for
NOTE
installed between the device and the UPS cabinet.
NOTE
conduit holes (see Drawing 164201535-6 on page A-27).
4. Remove the X-Slot conduit landing plate from the UPS cabinet to drill or punch
5. Reinstall the conduit landing plate.
6. Install conduit between the UPS and RMP. See Appendix A for UPS cabinet and
7. Install wiring between the UPS and RMP. See Drawing 164201535-8 starting on
NOTE
or the customer.
8. Install 120 Vac power wiring from the critical bus to the RMP. See Drawing
6-4
Only one system monitoring device can be connected to the Hot Sync CAN Bridge
Number and Type of Accessories Permitted
RMP
1
Chapter 10, "UPS Operating Instructions," for shutdown instructions.
If mounting to a hollow wall, secure the enclosure to a wood or metal stud within
mounting hole locations.
When installing signal wiring for CAN card J3 terminals, conduit must be
Remove the UPS cabinet top or bottom conduit landing plate to drill or punch
conduit holes (see Drawing 164201535-6 on page A-27).
RMP wiring access information.
page A-33 for Hot Sync CAN Bridge Card and RMP location, terminal location, and
wiring information.
120 Vac for the RMP should be supplied from the critical bus by facility planners
164201535-8 starting on page A-33 for terminal location and wiring information.
Powerware
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
®
RIM
1
SCM
1