Parallel system UPM and system bypass input feeds must come from the same source.
24.
Parallel UPM input wiring size requirements and output wiring size requirements from the
UPMs to the tie cabinet or distribution panel are the same as listed in Table E through
Table H.
25.
See Drawing 164201535 ---7 for UPM terminal locations and Table I or Table J for
termination requirements.
26.
Setup of the CAN Bridge card for parallel operation must be performed by an authorized
Powerware Customer Service Engineer . Contact service to schedule a date.
27.
For parallel system circuit breaker ratings, see appropriate information in Table O.
28.
For parallel system ratings, see the appropriate information in Table P through Table S.
Table O. Recommended UPM Output (MOB), Main Output (MIS), and Bypass (MBP)
UPM Model
Configuration
2+0 and 2+1
9390 40
9390---40
3+0 and 3+1
2+0 and 2+1
9390 50
9390---50
3+0 and 3+1
2+0 and 2+1
9390---60
9390 60
3+0 and 3+1
2+0 and 2+1
9390---80
9390 80
3+0 and 3+1
Powerware
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
®
Circuit Breaker Ratings
g
MOB
1+1
150
150
150
4+0
150
1+1
200
200
200
4+0
200
1+1
225
225
225
4+0
225
1+1
300
300
300
4+0
300
DESCRIPTION:
DRAWING NO:
REVISION:
Output Voltage
208V
MIS
MBP
MOB
150
150
70
300
300
70
450
450
70
600
600
70
200
200
80
350
350
80
600
600
80
700
700
80
225
225
100
500
500
100
700
700
100
1000
1000
100
300
300
125
600
600
125
1000
1000
125
1200
1200
125
POWER WIRING INSTALLATION NOTES
164201535---5
B
Installation Information
480V
MIS
MBP
70
70
150
150
200
200
250
250
80
80
175
175
250
250
350
350
100
100
200
200
300
300
400
400
125
125
250
250
400
400
500
500
SHEET:
11 of 16
DATE:
093004
A-21