Installation

Remote Emergency Power-Off

The Powerware 9125 includes a REPO port that allows power to be
switched off at the UPS output receptacles from a customer-supplied
switch in a remote location.
The REPO feature shuts down the protected equipment immediately and
does not follow the orderly shutdown procedure initiated by any power
management software.
Any devices that are operating on battery power are also shut down
immediately. When the REPO switch is reset, the equipment will not
return to battery power until the UPS is manually restarted.
If the Off
remains in Standby mode when restarted until the On button is
pressed.
The REPO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit
must be separated from any hazardous voltage circuits by reinforced insulation.
To ensure the UPS stops supplying power to the load during any mode of operation,
the input power must be disconnected from the UPS when the emergency power-off
function is activated.
NOTE The REPO function activates when the REPO contacts open.
NOTE If the REPO function is not needed, the REPO connector must remain installed
in the REPO port on the UPS rear panel.
NOTE For Europe, the emergency switch requirements are detailed in Harmonized
document HD-384-48 S1, "Electrical Installation of the Buildings, Part 4: Protection for
Safety, Chapter 46: Isolation and Switching."
Use the following procedure to install the REPO switch:
1. Verify that the UPS is off and unplugged (or the main utility
2. Remove the REPO connector from the REPO port on the rear
36
button is pressed after the REPO is activated, the UPS
W A R N I N G
C A U T I O N
breaker is off for hardwired units).
panel of the UPS.