Powerware 9390 Installation & Operation Manual page 197

40–80 kva
Hide thumbs Also See for 9390:
Table of Contents

Advertisement

114.3
(4.50)
TO UPS
Powerware
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
®
115.8
(4.56)
TO OTHER
EQUIPMENT
DESCRIPTION:
DRAWING NO:
REVISION:
11.9
(0.47)
NOTE: 1. Conduit and wiring between the
Remote Emergency Power ---Off (REPO)
and the UPS to be supplied by customer.
2. Maximum distance between the
Remote EPO and the UPS not to exceed
500 feet.
3. Maximum wire size #14 AWG.
Minimum wire size #22 AWG.
Dimensions are in millimeters [inches]
OPTIONAL REMOTE EMERGENCY
POWER-OFF
164201535---10
B
Installation Information
88.9
(3.50)
95.3
(3.75)
SQUARE
1/2 in. Knockout Pattern
typ. 5 sides
SHEET:
1 of 1
DATE:
111504
A-49

Advertisement

Table of Contents