Powerware 9390 Installation & Operation Manual page 170

40–80 kva
Hide thumbs Also See for 9390:
Table of Contents

Advertisement

Installation Information
Table P. INPUT/OUTPUT Ratings for Powerware 9390---40 Parallel System
Configuration
All
All
1+1
1+1
2+0
and
and
2+1
3+0
and
and
3+1
4+0
4+0
NOTE: Callout letters
and 5 of 5.
A-22
Basic Unit Rating at 0.9 lagging pF load
Input and Bypass Input
Output
AC Input from UPM
Full Load Current for each Module
(3) Phases, (1) Neutral, (1) Ground
Minimum Conductor Size for each Module
Number per Phase for each Module
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
F
G
,
, and
Powerware
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
®
Units
VOLTS
VOLTS
Amps
D
D
AWG or
kcmil
(each)
F
Amps
G
Amps
F
Amps
G
Amps
F
Amps
G
Amps
F
Amps
G
Amps
map to drawing 164201535 ---4, sheets 3 of 5, 4 of 5,
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201535---5
REVISION:
B
Rating 50/60 Hz
kVA
40
kW
36
208
208
111
See Table E through
Table H for wire size.
111
111
222
222
333
333
444
444
SHEET:
DATE:
093004
40
36
480
480
48
48
48
96
96
144
144
192
192
12 of 16