Powerware 9390 Installation & Operation Manual page 151

40–80 kva
Hide thumbs Also See for 9390:
Table of Contents

Advertisement

1.
The UPS equipment operating environment must meet weight requirements shown in
Table A and the size requirements shown on Drawing 164201535 ---9.
2.
The UPS cabinet is palleted separately for shipping.
3.
Do not tilt cabinets more than
4.
Dimensions are in millimeters (inches).
5.
The cabinet can be installed in line ---up–and–match or standalone configurations.
Table A. Equipment Weight
Table A Equipment Weight
Component/Model
Component/Model
UPS Cabinet/9390---40 kVA, 208V/208V
UPS Cabinet/9390---40 kVA, 480V/480V
UPS Cabinet/ 9390---50 kVA, 208V/208V
UPS Cabinet/ 9390---50 kVA, 480V/480V
UPS Cabinet/9390---60 kVA, 208V/208V
UPS Cabinet/9390---60 kVA, 480V/480V
UPS Cabinet/9390---80 kVA, 208V/208V
UPS Cabinet/9390---80 kVA, 480V/480V
6.
The clearances required around the UPS cabinet are shown in Table B.
Table B. UPS Cabinet Clearances
From Top of Cabinet
From Front of Cabinet
From Back of Cabinet
From Right Side of Cabinet
From Left Side of Cabinet
Powerware
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
®
10˚ during handling.
Shipping
313 (690)
271 (618)
313 (690)
271 (618)
313 (690)
271 (618)
313 (690)
271 (618)
Minimum clearance over the UPS cabinet is
457.2 mm (18 in.) for ventilation
36 inches working space
None Required
None Required
None Required
DESCRIPTION:
PHYSICAL FEATURES AND REQUIREMENTS
DRAWING NO:
164201535---2
REVISION:
B
Installation Information
Weight
kg (lb)
Installed
Point Loading
290 (640)
4 at 72.5 (160)
258 (568)
4 at 64.5 (142)
290 (640)
4 at 72.5 (160)
258 (568)
4 at 64.5 (142)
290 (640)
4 at 72.5 (160)
258 (568)
4 at 64.5 (142)
290 (640)
4 at 72.5 (160)
258 (568)
4 at 64.5 (142)
SHEET:
DATE:
111504
1 of 2
A-3