Powerware 9390 Installation & Operation Manual page 174

40–80 kva
Hide thumbs Also See for 9390:
Table of Contents

Advertisement

Installation Information
29.
Required parallel system wiring length should be in accordance with the following rule, as
referenced to the diagram below, to ensure approximately equal current sharing, when in
static bypass mode:
(Total length of 1A + 1B)  (Total length of 2A + 2B)  (Total length of 3A + 3B)  (Total length of 4A + 4B)
This rule has a tolerance of approximately H10% for the combined input and output wire
lengths.
If installing only two UPMs in a fully redundant system, this requirement is no longer
required, as each UPM is capable of supporting the full bypass requirement. However, this
would preclude future expansion.
Bypass inputs to UPMs
2A
3A
4A
A-26
1A
Powerware
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
®
UPM 1
Battery
UPM 2
Battery
UPM 3
Battery
UPM 4
Battery
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201535---5
REVISION:
B
Outputs from UPMs
1B
2B
3B
4B
SHEET:
16 of 16
DATE:
093004