Powerware 9390 Installation & Operation Manual page 164

40–80 kva
Hide thumbs Also See for 9390:
Table of Contents

Advertisement

Installation Information
Table J. UPS Cabinet Power Cable Terminations Powerware 9390---40, 9390---50 9390---60,
Terminal Function
AC Input to UPS Rectifier
p
and Bypass
d B
(Single Input)
(Single Input)
AC Input to UPS Rectifier
p
(D
(Dual Input)
l I
)
AC Input To Bypass
p
(D
(Dual Input)
l I
)
Single Feed Jumper from
g
Rectifier Input Terminals
R
ifi
I
to Bypass Input Terminals
to Bypass Input Terminals
AC Output to
p
C i i
Critical Load
l L
d
DC Input from
p
Battery to UPS
B
UPS
Input and Output Neutral
Customer Ground
NOTE: Customer ground can be run in any conduit listed in Table K.
A-16
and 9390---80 (480V/480V)
Terminal Function
E6
E7
E8
E1
E2
E3
yp
E6
E7
E8
p
T
i
l
E9
E10
E11
E4
E5
Negative
E12
Ground
Powerware
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
®
Size of Pressure
Termination
Phase A
1 --- #14---2/0
Phase B
1 --- #14---2/0
Phase C
1 --- #14---2/0
Phase A
1 --- #14---2/0
Phase B
1 --- #14---2/0
Phase C
1 --- #14---2/0
Phase A
1 --- #14---2/0
Phase B
1 --- #14---2/0
Phase C
1 --- #14---2/0
Phase A
N/A
Phase B
N/A
Phase C
N/A
Phase A
1 --- #14---2/0
Phase B
1 --- #14---2/0
Phase C
1 --- #14---2/0
Positive
1 --- #6---500 kcmil
1 --- #6---500 kcmil
Neutral
4 --- #14---1/0
Ground
8 --- #14---1/0
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201535---5
REVISION:
B
Tightening
Type
Torque
Nm (lb in)
Screw
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
5.6 (50)
1/4–20 Hex Nut
5.6 (50)
1/4–20 Hex Nut
5.6 (50)
1/4–20 Hex Nut
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
56.5 (500)
1/2 in. Hex
56.5 (500)
1/2 in. Hex
5.6 (50)
Slotted
5.6 (50)
Slotted
SHEET:
DATE:
111504
6 of 16