3.2.5.3 X-Slot Connections

For installation and setup of an X-Slot card, please contact Powerware (see page 1-6).
To install wiring for connections:

3.2.6 Installing Accessories and Parallel System Control Wiring

To install an optional Remote Emergency Power-Off Control, see Chapter 5, "Installing a
Remote Emergency Power-Off Control." To install optional accessories, see Chapter 6,
"Installing Options and Accessories." To install parallel system control wiring, see Chapter 6,
"Installing Options and Accessories."

3.3 Initial Startup

Startup and operational checks must be performed by an authorized Powerware Customer
Service Engineer, or the warranty terms as specified on page W-1 become void. This service
is offered as part of the sales contract for the UPS. Contact service in advance (usually a
two-week notice is required) to reserve a preferred startup date.
Powerware
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
®
NOTE
LAN and telephone drops for use with X-Slot connectivity cards must be provided
by facility planners or customer.
When installing external wiring to X-Slot cards, conduit must be installed to the
NOTE
UPS cabinet. When installing internal wiring to X-Slot terminals, route the wiring
through the internal opening in the X-Slot communication bay.
1. If not already installed, install the LAN and telephone drops.
2. Unfasten the front door latch and swing the door open.
3. Remove the UPS cabinet X-Slot conduit landing plate to drill or punch conduit
holes (see Drawing 164201535-6 on page A-27).
4. Reinstall the conduit landing plate and install the conduit.
5. Route and install the LAN, telephone, and other cables to the appropriate X-Slot
cards.
6. When all wiring is complete, reinstall the safety shield panels removed in previous
steps. Secure with the retained hardware.
7. Close the control panel door and secure with the retained hardware.
8. Reinstall the door removed in Step 3 or paragraph 3.2.1 and secure with the
retained hardware.
9. Close the door and secure the latch.
10. Refer to the manual supplied with the X-Slot card for user instructions.
Installing the UPS System
3-11