6.4

Basic parameters 2

6.4.1
Switching motor characteristics via terminal input
 : Base frequency 2
 : Base frequency voltage 2
 : Torque boost value 2
 : Motor electronic-thermal protection level 2
 : Stall prevention level 2
 Function
Use the above parameters to switch the operation of two motors with a single inverter and to select
motor V/F characteristics (two types) according to the particular needs or operation mode.
Note: The  (V/F control mode selection) parameter is enabled only for motor1.
If motor 2 is selected, V/F control will be given constant torque characteristics.
[Parameter setting]
Title
Base frequency 2


Base frequency voltage 2
Torque boost value 2

Motor electronic-thermal

protection level 2
Stall prevention level 2

*1:
Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*2:
The inverter's rated current is 100%. When  (current and voltage unit selection)
=  (A (amps)/V (volts)) is set, it can be set at A (amps).
Function
25.0-400.0 (Hz)
50-330 (V)
0.0-30.0 (%)
10-100 (%) / (A) *2
10-199 (%) / (A), *2
200 : Disabled
F-9
Adjustment range
Depending on model
(Refer to section 11.4)
E6581595
6
Default setting
*1
*1
100
150