MX2820 System Manual
Table 7-7
provides the configuration recommendations for circuit recovery.
During a module switch, service interruption is experienced on
both the DS3/STS-1 and T1/E1 connections. However, since the
standby module remains framed to the incoming signal at all
times, it is a minimal interruption.
Table 7-7. Configuration Recommendations for Circuit Recovery
Parameter
Network XCV Threshold
Maximum Switch Threshold
Minimum Switch Period
T1/E1 Circuit Protection
T1/E1 XCV Threshold
MUX MODULE PROTECTION DATA
Provisioning data includes the following:
• Manual switch of protection
• Minimum switching period
• Maximum switch threshold
In the case of 1:1 protection, provisioning the Active MUX module
automatically provisions the Standby MUX module.
PROCEDURE
1. If not already connected, connect the VT100 terminal or PC to the craft port. For details,
refer to DLP-715.
2. Logon to the MX2820 system. For details, refer to DLP-716.
3. From the MX2820 Main Menu, select
menu screen displays.
7-152
NOTE
Recommended Setting
1E-3 (The XCV Threshold settings are based on the error
rates considered acceptable on the DS3 or DS1 before
switching.)
3
10 seconds
Enable all or select the T1/E1s where redundant switch-
ing should occur
1E-3 (The XCV Threshold settings are based on the error
rates considered acceptable on the DS3 or DS1 before
switching.)
NOTE
and press
A
M
CCESS
ODULE
. The Access Modules