Verifying Alarm Relay Output Connections

INTRODUCTION

This procedure provides step-by-step instructions to verify the MX2820 shelf's external alarm
relay outputs are properly connected to any office alarm equipment.
This procedure should be performed after the installation for each MX2820 shelf that is wired
to external office alarm equipment.

PREREQUISITE PROCEDURES

The following procedure must be completed before verifying alarm relay output connections. If
necessary, refer to the appropriate documentation before proceeding.
• "DLP-506,
Connect MX2820 Wire-Wrap Posts"

MATERIALS REQUIRED

• VT100 terminal or PC with VT100 terminal emulation software
To prevent electrical shock, do not install equipment in a wet loca-
tion or during a lightning storm.
Electronic modules can be damaged by static electrical discharge.
Before handling modules, wear an antistatic discharge wrist strap
to prevent damage to electronic components. Place modules in
antistatic packing material when transporting or storing. When
working on modules, always place them on an approved antistatic
mat that is electrically grounded.
61186003L1-1D
DLP-724
WARNING
CAUTION
7-99