Omron DEVICENET SAFETY - 03-2008 Operation Manual page 128

Safety i/o terminals
Table of Contents

Advertisement

DeviceNet Explicit Messages
Explicit
Read/
message
write
Input Monitor
Read
Reads the set
Status for
value for the total
Total ON
ON time (unit: s) or
Time or Con-
number of contact
tact Opera-
operations (unit:
tion Counter
operations) of the
Read
input (1 to 12)
specified by the
instance ID.
Safety Input
Read
Reads the cause
Cause of
for the normal flag
Error Informa-
(1 to 12) specified
tion Read
by the Instance ID
turning OFF.
Function
Service
Code
0E hex
3D hex 01 to 0C
0E hex
3D hex 01 to 0C
Command
Class
Instance
Attribute
ID
ID
ID
67 hex
hex
6E hex
hex
Appendix 1
Response
Data size
1 byte
00 hex: Within
range
01 hex: Over
range (over the
monitor value)
0: No error
01 hex: Con-
figuration invalid
02 hex: External
wiring error
03 hex: Internal
input failure
04 hex: Two-input
logic discrepancy
05 hex: Error in
the other dual
channel input
107