General Parameters - Omron DEVICENET SAFETY - 03-2008 Operation Manual

Safety i/o terminals
Table of Contents

Advertisement

Editing Device Parameters
3-1-2

General Parameters

Parameter name
S
Safety Output Error
Latch Time
S
Safety Input Error Latch
Time
--- Test Output Idle State
--- Unit Name
--- Threshold Network
Power Voltage
--- Threshold Run Hours
--- Last Maintenance date
S
Execution Mode (DST1-
XD0808SL-1 only)
IMPORTANT If the power is turned OFF in Idle Mode, the next operation will not start in
IMPORTANT Safety I/O communications cannot be used when Auto Execution is set as the
Value
0 to 65,530 ms
(in increments of 10 ms)
0 to 65,530 ms
(in increments of 10 ms)
Clear OFF
Keep output data
32 characters max.
8.0 to 30.0 V
0 to 429,496,729 hours
1972/01/01 to
2038/01/19
After Establishing Safety
I/O Connection
Auto Execution
RUN Mode even if Auto Execution is set as the execution mode and the con-
figuration is locked. The power must be turned OFF in RUN Mode.
execution mode. To use safety I/O communications, set After Establishing
Safety I/O Connection as the execution mode.
Description
This parameter is common to all the safety out-
puts.
It sets the time to latch the error state when an
error occurs in these outputs. Even when the
cause of the error has been removed, the error
state will remain latched for the time set here.
This parameter is common to all safety inputs
and test outputs.
It sets the time to latch the error state when an
error occurs in these inputs/outputs. Even when
the cause of the error has been removed, the
error state will remain latched for the time set
here.
This parameter is common to all test outputs for
which the Test Output Channel Mode is set to
Standard Output. It sets the output state of the
test output when idle data is received.
This parameter sets a user-chosen name for the
DST1-series Safety I/O Terminals. The set name
is saved in the DST1-series Safety I/O Terminals
and displayed in the network configuration.
This parameter sets the threshold of the network
power voltage. When the voltage falls below the
set threshold voltage, the corresponding bit in
general status turns ON.
This parameter sets the threshold for unit operat-
ing hours. When the operating hours exceeds the
set threshold, the corresponding bit in general
status will turn ON.
This parameter saves the maintenance date in
the DST1-series Safety I/O Terminals.
Starts in Idle Mode after the configuration has
been completed. Goes into RUN Mode when
safety I/O communications are started.
Selecting this mode and executing the following
operations causes startup in RUN Mode from that
point onwards.
• Locking the configuration
• Turning OFF the power after changing to RUN
Mode
Safety I/O communications are not possible in
this mode.
Section 3-1
Default
1,000 ms
1,000 ms
Clear OFF
None
11 V
0 hours
1972/01/01
After Estab-
lishing
Safety I/O
Connection
31