DeviceNet Explicit Messages
Setting and Monitoring the Test Output Point
Explicit
Read
message
/write
Terminal Main-
Read Reads the monitor
tenance Infor-
mode for mainte-
mation Monitor
nance information
Mode Read
of the output (1 to
4) specified by the
instance ID.
Write Writes the monitor
mode for mainte-
nance information
of the output (1 to
4) specified by the
instance ID
Output Set
Read Reads the set value
Value for Total
for the total ON
On Time or
time (unit: s) or
Contact Opera-
number of contact
tion
operations (unit:
operations) of the
output (1 to 4)
specified by the
instance ID.
Write Writes the set value
for the total ON
time (unit: s) or
number of contact
operations (unit:
operations) of the
output (1 to 4)
specified by the
instance ID.
Output Total
Read Reads the set value
ON Time or
for the total ON
Contact Opera-
time (unit: s) or
tion Counter
number of contact
Read
operations (unit:
operations) of the
output (1 to 4)
specified by the
instance ID.
Output Total
Reset Resets the total ON
ON Time or
time or number of
Contact Opera-
contact operations
tion Counter
for time output (1 to
Reset
4) specified by the
instance ID.
110
Function
Service
Code
0E hex
09 hex 01 to 04
10 hex
09 hex 01 to 04
0E hex
09 hex 01 to 04
10 hex
09 hex 01 to 04
0E hex
09 hex 01 to 04
05 hex
09 hex 01 to 04
Command
Class
Instance
Attribute
ID
ID
ID
65 hex
hex
65 hex
hex
68 hex
hex
68 hex
hex
66 hex
hex
66 hex
hex
Appendix 1
Response
Data size
-
1 byte
00 hex: Total ON
time mode
01 hex: Contact
operation
counter mode
1 byte
-
00 hex: Total
ON time mode
01 hex: Contact
operation
counter mode
-
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295)
4 bytes
-
0000 0000 to
FFFF FFFF
hex
(0 to
4,294,967,295)
-
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295)