Error Log
Error
Contents
code
0109
Transmission failed; destination
Hex
busy
010A
Transmission failed; communica-
Hex
tions controller error
010B
Transmission failed; PLC error
Hex
010C
Transmission failed; unit number
Hex
incorrect
010D
Transmission failed; destination
Hex
address incorrect
010E
Transmission failed; routing
Hex
tables not registered
010F
Transmission failed; routing table
Hex
error
0110
Transmission failed; too many
Hex
relay points
0111
Transmission failed; command
Hex
packet too long
0112
Transmission failed; header
Hex
error.
0113
Transmission failed; I/O setting
Hex
error
0114
Transmission failed; CPU bus
Hex
error
0115
Transmission failed; redundant I/
Hex
O allocations
0116
Transmission failed; CPU Bus
Hex
Unit error
140
Detail code
1st byte
2nd byte
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Source Network address
Bit 15:
OFF
Response block
Bits 0 to 7:
Destination node address
Bits 8 to 14:
Destination Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
Correction
Set the data link tables com-
munications cycle time auto-
matically, or increase the
settings manually.
Conduct an echoback test
and if the effects of noise are
considerable, reconsider the
operating environment.
Restart the SYSMAC LINK
Unit. If the error occurs again,
replace the Unit.
Refer to the PLC operating
manual. If the error occurs
again, replace the PLC.
Check unit number settings to
be sure they are within range
and unique.
Check routing tables.
Check routing tables.
Check routing tables.
Check routing tables and sys-
tem configuration. Do not try
to access Networks sepa-
rated by more than one other
Network.
Be sure to use the FINS com-
mand format.
Be sure to use the correct
FINS command format.
Check I/O table accuracy.
Check Unit and cable connec-
tions and clear error.
Check unit numbers for
redundancy within the same
PLC.
Check Unit and cable connec-
tions and clear error.
Section 8-2
Written to
EEPROM
No
Yes
No
No
No
No
No
No
No
No
No
No
No
No

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Sysmac cs1w-slk11Sysmac cs1w-slk21

Table of Contents