Command/Response Parameters; Communications Data Format - Omron CS1W-SLK11-21 - 06-2004 Manual

Sysmac link units
Table of Contents

Advertisement

FINS Command/Response Format
Types of FINS Commands
6-3-2

Command/Response Parameters

6-3-3

Communications Data Format

Command Format
Response Format
3. FINS commands support network relay operations, so they can pass
through a network hierarchy to access devices on up to three network lev-
els (including the local network).
Network 1
There are basically two kinds of FINS commands: Those addressed to CPU
Units and those addressed to CS-series CPU Bus Units. Among FINS com-
mands for CPU Units, there are commands addressed to the various models
of CPU Unit, such as the CS-series CPU Units, CV-series CPU Units,
C200HX/HG/HE CPU Units, and so on. The basic code system is the same,
but the detailed specifications vary according to the CPU Unit.
Among FINS commands for CS-series CPU Bus Units, there are commands
addressed to SYSMAC LINK Units, to the Controller Link Unit, and so on.
All parameters used in commands and responses are in hexadecimal, unless
otherwise specified.
Commands have the following format. This data must be stored beginning at
first command word specified as an operand (S) of the CMND(490) instruc-
tion.
2 bytes
Command
code
Responses have the following format and are stored beginning at the first
response word specified as an operand (D) of the CMND(490) instruction.
2 bytes
2 bytes
01
01
Command
Response
code
code
Network 2
540 bytes max.
Data
538 bytes max.
Data
Section 6-3
Network 3
109