Remote Programming and Monitoring
7-1-3
Remote Programming and Monitoring Different Networks
CX-Programmer
Programming Device
CX-Programmer
Note Remote programming and monitoring is possible from computer nodes.
Note
You can program and monitor CPU Units on different networks (Ethernet,
SYSMAC NET, and Controller Link) from a CX-Programmer connected to a
CS-series, CVM1/CV-series, or C200HX/HG/HE-series CPU Unit. CS-series,
CVM1, and CV-series PLCs must be used as the bridges between the net-
works.
SYSMAC LINK Network
CS-series, CVM1, CV-series, or
C200HX/HG/HE-series PLC
SYSMAC LINK
C200HX/HG/HE
CS-series PLC
When performing remote programming or monitoring from CX-Programmer
over a SYSMAC LINK Network, set the frame length to a maximum of 542
bytes using the network settings of the PLC connected to CX-Programmer. If
the frame length is set to 543 bytes or over, the user program and other data
cannot be transferred.
Controller Link Network,
Ethernet Network, etc.
CS1
Controller Link,
Ethernet, etc.
CVM1 or
CV-series PLC
Section 7-1
Programming/
Monitoring
CS, CVM1, or
CV-series PLC
125